Measurement
NanoVIP® TWO™
Portable power quality analyzer
NanoVIP® TWO™ is a modern, compact and powerful portable Power Quality analyzer for professional use in the most complex electrical networks.
It can be used on single-phase, two-phase, three-phase balanced networks, low and medium voltage.
A long lasting battery (over 24h with one charge) and the huge logging capability of data (over 1 year) are distinguishing characteristics that make it an absolute reliable and professional tool.
Measurement precision,
easiness of use
- Light, handy, multilingual, with performance and features at the top of its class
- LCD graphic display that allows wide flexibility in the (multilingual menu, waveforms, histograms, personalized pages, drawings, diagrams, pictures, etc.)
- PC Software NonoStudio dedicated through which you can make advanced analysis of the data stored on uSD
- 1 voltage measuring channel (1 phase + neutral) up to 600V CAT III, with the possibility to also measure the DC voltage, with the precision of the 0,25% + err.FS
- 1 current input with the possibility to also measure the DC current, with the precision of the 0,25% + err.FS
- Automatic verification of the correctness of the device connected to the network
- Possibility to use flexible current probe up to 3000A or other captors with full scale set by the user
- High capacity batteries that allow a range of campaign more than 24 hours even in the absence of mains power; no country limit when connected to the network
- Calculation engine Powerful allowing besides the measuring of all standard electrical parameters (V I P Q A F PF THD% etc.) True RMS (TRMS): harmonics up to the 50th, dips, swells, micro interruptions and many other
- 20 alarms (generic, swells, dips and interruptions)
- Energy Measurement in 4 time zones (rates) set
Fields of use
The NanoVIP® TWO™ is a handy tool, compact and light aimed at both those who want to work on their equipment than with industry professionals who need detailed and accurate analysis of power quality; NanoVIP® TWO™ allows in an easy and intuitive way:
- to control the loads, consumption and the associated network costs
- check in service the correct dimensioning of plants
- to prevent the risk for overheating and insulation failures due to high harmonic content
- correct the power factor problems
- Identify and eliminate load peaks and exceed power in order also to reduce the bargaining power commitment
- check and evaluate the returns of UPS, AC / DC measurements
- Measure signals for non-symmetric PWM control of inverter
- Identify the presence of harmonics, outages, overloads or potentially harmful voltage dips for machinery and equipment
- Intercept fluctuations and rapid changes in current and voltage signals
- Measure the inrush currents of motors and electrical machinery
Brochure NanoVIP® TWO™ 735 kb 814 downloads
Power Quality analyzer for monophase, biphase and three phase balanced networks ...| Standard | IEC61000-4-30 Class S |
| Dimensions | 203x116x53mm |
| Safety | 600V CAT III |
| Protection degree | IP30 |
| Weight | 580g. |
| Display type | LCD dot matrix with backlight |
| Languages | English- Spanish – Italian – German – French |
| Communication | USB to PC |
| Onboard memory | 64kB |
| External memory | Micro SD (4GB supplied) |
| Working temperature range | from -10 to +55 °C |
| Umidity | Max 95% |
| External power supply | Wall-plug switching, input 100-240VAC ±10% 47-63Hz, changeable plug; output 7,5VDC – 12W |
| Battery | 4 x AA MiMh 2100mAh |
| Autonomy | >24h |
| Single phase/Double phase networks | yes |
| Three phase 4 wires, balanced networks | yes |
| Three phase 3 wires, balanced networks | yes |
| Three phase 4 wires, unbalanced networks | no |
| Three phase 3 wires, unbalanced networks | no |
| Power analisys | V, I, P, Q, S, F, PF, THD(V)%, THD(I)%, cosj, j, peaks, min, max, mid, max. demand, ecc. |
| Counters | kWh, kVArh, kVAh (used and generated) |
| Waves shape | V e I |
| Harmonics | Values and spectrum up to 50° |
| Sags | Dips, swells and net interruption |
| Transitory | Overcurrent and overtension |
| Test EN 50160 | yes |
| Starting currents | yes |
| Measurements in DC | yes |
| K factor | Up to 25° |
| Alarms | Video |
| Alarms logs | 5 on video |
| Hourly tarifs | up to 4 |
| Consumption costs | yes |
| Measurement campaign | Unlimited, up to SD completition |
| Display data refres | 1 sec. |
| Voltage (TRMS) | 1 input channel 4MOhm, 2 scales |
| Current (TRMS) | 1 input channel 10kOhm |
| Power | Active, reactive and apparent. Single phase and total |
| Energy counters | kWh, kvarh, kVAh |
| Harmonics analisys | Up to 50° |
| EN50160 analisys | from 500mS up |
| Transitional analisys | Overcurrent, overvoltage and starting currents |
| CE conformity | 93/68/CEE (B.T. electrical materials); |
| 89/336/CEE e 2004/108/CE (EMC) | |
| 2006/95/CE – 72/23/CEE (LVD – Low voltages); | |
| 2002/95/CE (RoHS – Dangerous materials restrictions); | |
| 2002/96/CE e 2003/108/CE (WEEE/RAEE – Wasted electrical and electronics materials). | |
| Safety | EN 61010-1 |
| EMC | EN 61326 |
| EN 61326/A1 | |
| EN 61326/A2 | |
| EN 61326/A3 | |
| Temperature | IEC 60068-2-1 (working) |
| IEC 60068-2-2 (storage) | |
| Vibrations | IEC 60068-2-6 |
| Umidity | IEC 60068-2-30 (umidity) |
| Overload | IEC 60947-1 |
| 4NAN2N | NANOVIP/TWO WITHOUT CLAMP |
| 4NAN2 | NANOVIP/TWO WITH NANOFLEX CLAMP 400mm 3kA |
| 4NAN2A | NANOVIP/TWO WITH CLAMP CT 200A/1VAC |
| 4NAN2B | NANOVIP/TWO WITH CLAMPS 1x200A + 1x3kA |
| 4NAN2C | NANOVIP/TWO WITH CLAMPS 1x200A + 1x5A |
| 4NAN2D | NANOVIP/TWO WITH CLAMPS 1x200A + 1x1000A |
| 4NAN2E | NANOVIP/TWO WITH CLAMPS 1x1000A |
| PART | Quantity | Standard/Option |
| NanoVIP TWO | 1 | Standard |
| Battery pack | 1 | Standard |
| Voltage cables | 2 | Standard |
| Crocodiles | 2 | Standard |
| mSD 4Gb | 1 | Standard |
| mSD adaptor | 1 | Standard |
| External power supply + adapters | 1 | Standard |
| Bag | 1 | Standard |
| Carton box | 1 | Standard |
| Calibration certificate | 1 | Standard |
| AC Current probes | 1 or more | Option – According to package |
| DC Current clamp | 1 or more | Option – According to package |